| MODEL |
RCT-INFINI V4 5.6K48V |
| PHASE |
1-phase in/ 1-phase out |
| Maximum PV Input Power |
6000W |
| Rated Output Power |
5600W |
| Maximum Charging Power |
6000W |
| GRID-TIE OPERATION |
| PV INPUT (DC) |
| Nominal DC Voltage/ Maximum DC Voltage |
360VDC /450 VDC |
| Start-up Voltage/ Initial Feeding Voltage |
110VDC /120 VDC |
| MPP Voltage range |
120VDC – 430VDC |
| Number of MPP Trackers/ Maximum Input Current |
1 / 27A |
| GRID OUTPUT (AC) |
| Nominal Output Voltage |
220/230/240 VAC |
| Output Voltage Range |
184 – 264.5 VAC or 195.5 – 253 VAC (Selectable) |
| Nominal Output Current |
24.3 A |
| Power Factor |
>0.9 |
| EFFICIENCY |
| Maximum Conversion Efficiency (DC/AC) |
96% |
| OFF-GRID OPERATION |
|
| AC INPUT |
|
| AC Strt-up voltage / Auto re-start voltage |
120 – 140VAC / 180VAC |
| Acceptable Input Voltage Range |
90 – 280 VAC or 170 – 280 VAC |
| Maximum AC Input Current |
40 A |
| PV INPUT (DC) |
| Maximum DC Voltage |
450 VDC |
| MPP Voltage Range |
120 VDC – 430 VDC |
| Number of MPP Trackers/ Maximum Input Current |
1 / 27A |
| BATTERY MODE OUTPUT (AC) |
| Nominal Output Voltage |
220/230/240 VAC |
| Output Waveform |
Pure sine wave |
| Efficiency (DC to AC) |
93% |
| HYBRID OPERATION |
| PV INPUT (DC) |
| Nominal DC Voltage/ Maximum DC Voltage |
360VDC /450 VDC |
| Start-up Voltage/ Initial Feeding Voltage |
110VDC /120 VDC |
| MPP Voltage Range |
120VDC – 430VDC |
| Number of MPP Trackers/ Maximum Input Current |
1 / 27A |
| GRID OUTPUT (AC) |
| Nominal Output Voltage |
220/230/240 VAC |
| Output Voltage Range |
184 – 264.5 VAC or 195.5 – 253 VAC (Selectable) |
| Nominal Output Current |
24.3 A |
| AC INPUT |
| AC Strt-up voltage / Auto re-start voltage |
120 – 140VAC / 180VAC |
| Acceptable Input Voltage Range |
90 – 280 VAC or 170 – 280 VAC |
| Maximum AC Input Current |
40 A |
| BATERY MODE OUTPUT (AC) |
| Nominal Output Voltage |
220/230/240 VAC |
| Efficiency (DC to AC) |
93% |
| BATTERY & CHARGER |
| Nominal DC Voltage |
48 VDC |
| Maximum Solar Charging Current |
120 A |
| Maximum AC Charging Current |
120 A |
| Maximum Charging Current |
120 A |
| GENERAL |
| PHYSICAL |
| Dimension, D x W x H (mm) |
140 x 295 x 468 |
| Net Weight (kgs) |
12 |
| INTERFACE |
| Parallel Function |
Yes, 9 units |
| Communication Ports |
USB, RS-232. RS485, WiFi and dry contact |
| ENVIRONMENT |
| Operating Humidity |
0 ~ 90% RH (Non-condensing) |
| Operating Temperature |
-10°C to 50°C |